Atac Technology Co., Ltd.

Modbus - Serial - Ethernet - WiFi - Fiber - Digital IO - Analog IO

  • Increase font size
  • Default font size
  • Decrease font size

SE-130WA - How to set up SE-130WA for one RS-485 PLC communicating to many RS-485 PLC over WiFi ?

E-mail Print

For one primary PLC communicating to many coworking PLCs, it is strongly recommended to use an industrial AP router as the access point for all SE-130WA converters.

Prepare an AP router and turn it on, so the AP router's SSID can be detected by all SE-130WA converters.

For SE-130WA connecting to primary PLC:
Set as Server mode.
Set SSID as AP router's SSID.
Set Network type as "Infra".

For all SE-130WA connecting to coworking PLC:
Set as Client mode.
Set SSID as AP router's SSID.
Set Network type as "Infra".
Set Destination IP as the wireless IP of the SE-130WA connecting to primary PLC.