How to set up SE130WA for one RS485 PLC communicating to many RS485 PLC over WiFi

For one primary PLC communicating to many coworking PLCs, it is strongly recommended to use an industrial AP router as the access point for all SE130WA converters.

Prepare an AP router and turn it on, so the AP router’s SSID can be detected by all SE130WA converters.

For SE130WA connecting to primary PLC
Set as Server mode.
Set SSID as AP router’s SSID.
Set Network type as “Infra”.

For all SE130WA connecting to coworking PLC
Set as Client mode.
Set SSID as AP router’s SSID.
Set Network type as “Infra”.
Set Destination IP as the wireless IP of the SE130WA connecting to primary PLC.