Modbus RTU Analog Input and Analog Output

AM142

TI chipset 16-bit resolution
4 x Analog input data acquisition
2 x Analog output
Selective as 0~10 V DC and 4~20 mA by jumper settings

OverviewSpecificationsInquiryResources

Reading voltage and amperage value from analog input using Modbus RTU.

Sending command to analog output setting up voltage and amperage value using Modbus RTU.

 

 

Easy setup by software

 

Test and change baud rate and change device ID

 

Selective as 4~20 mA and 0~10 V DC by jumper settings

CPU 8-bit CPU
RAM 64K bytes SRAM
ROM 256K bytes Flash ROM
Analog input TI chipset 16-bit resolution
4 channels
Selective as 0~10 V DC and 4~20 mA by jumper settings
Sample rate : 5 times / second (4 channels)
Analog output 12-bit resolution
Selective as 0~10 V DC and 4~20 mA by jumper settings
Serial RS485 x 1 port ( Terminal Block )
Speed : 9600 bps ~ 115.2 Kbps
Parity : None
Data Bit : 8
Stop Bit : 1
Surge Protect
Modbus protocol type Modbus RTU
Watch Dog function Yes
Power supply DC 9 ~ 24 V , 300mA @ 12VDC
Support DC Jack and Terminal Block
LED Indicator PWR, Rx, Tx
Operating Temperature -10℃ ~ +70℃
Storage Temperature -20℃ ~ +85℃
Dimension 90 x 60 x 20 mm ( W x D x H )
Weight 140 g
Din rail panel mounting kit Optional
Approvals CE, FCC, RoHS
Warranty 1 year

 